Advantech WebAccess SCADA
1. EXECUTIVE SUMMARY
- CVSS v3 4.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Advantech
- Equipment: WebAccess SCADA
- Vulnerability: Missing Authorization
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to access project names and paths.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of WebAccess/SCADA, an HMI platform, are affected:
- WebAccess/SCADA: Versions 9.0.3 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 MISSING AUTHORIZATION CWE-862
An authenticated user can use API functions to disclose project names and paths from other users.
CVE-2021-38431 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: East Asia, United States, Europe
- COMPANY HEADQUARTERS LOCATION: Taiwan
3.4 RESEARCHER
Peter Cheng from ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc., reported this vulnerability to CISA.
4. MITIGATIONS
Advantech recommends users upgrade to v9.1.1 or later.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Advantech