Mitsubishi Electric MELSEC-F Series
1. EXECUTIVE SUMMARY
- CVSS v3 7.5
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Mitsubishi Electric
- Equipment: MELSEC-F Series
- Vulnerability: Lack of Administrator Control Over Security
2. RISK EVALUATION
Successful exploitation of this vulnerability could lead to a denial-of-service condition in the communication function of the product or cause other unspecified effects.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of MELSEC-F Series with FX3U-ENET, an Ethernet-Internet block, are affected:
- FX3U-ENET Firmware Version 1.14 and prior
- FX3U-ENET-L Firmware Version 1.14 and prior
- FX3U-ENET-P502 Firmware Version 1.14 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 LACK OF ADMINISTRATOR CONTROL OVER SECURITY CWE-671
The affected product is vulnerable due to a lack of administrative controls, which may allow an attacker to remotely send specially crafted packets and cause a denial-of-service condition or other unspecified effects.
CVE-2021-20612 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Japan
3.4 RESEARCHER
Mitsubishi Electric reported this vulnerability to CISA.
4. MITIGATIONS
Mitsubishi Electric corrected this vulnerability in the following products and versions:
- FX3U-ENET: Firmware Version 1.16 or later
- FX3U-ENET-L: Firmware Version 1.16 or later
- FX3U-ENET-P502: Firmware Version 1.16 or later
Mitsubishi Electric recommends users to take the following mitigations:
- Use a firewall or virtual private network (VPN) to prevent unauthorized access when Internet access is required.
- Use within a LAN and block access from untrusted networks and hosts through firewalls.
Please contact Mitsubishi Electric Support for assistance and review the Mitsubishi Electric security advisory for more information about this issue.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Mitsubishi Electric