ICS Advisory

Siemens Multiple Vulnerabilities in SCALANCE Products

Last Revised
Alert Code
ICSA-22-349-04

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

1. EXECUTIVE SUMMARY

  • CVSS v3 7.6
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: RUGGEDCOM and SCALANCE devices
  • Vulnerabilities: Code Injection, Use of a Broken or Risky Cryptographic Algorithm, Storing Passwords in a Recoverable Format, Improper Validation of Specified Quantity in Input, Improper Control of a Resource Through its Lifetime

2. RISK EVALUATION

Successful exploitation of these vulnerabilities would allow an attacker to execute arbitrary code with elevated privileges or retrieve user credentials and other sensitive information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

  • RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M804PB (6GK5804-0AP00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M812-1 ADSL-Router (Annex A) (6GK5812-1AA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M812-1 ADSL-Router (Annex B) (6GK5812-1BA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M816-1 ADSL-Router (Annex A) (6GK5816-1AA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M816-1 ADSL-Router (Annex B) (6GK5816-1BA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M874-2 (6GK5874-2AA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M874-3 (6GK5874-3AA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M876-3 (EVDO) (6GK5876-3AA02-2BA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M876-4 (6GK5876-4AA10-2BA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE S615 (6GK5615-0AA00-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE S615 EEC (6GK5615-0AA01-2AA2) (only affected by CVE-2022-34821, CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE SC622-2C (6GK5622-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC622-2C (6GK5622-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE SC626-2C (6GK5626-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC626-2C (6GK5626-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE SC632-2C (6GK5632-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC632-2C (6GK5632-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE SC636-2C (6GK5636-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC636-2C (6GK5636-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE SC642-2C (6GK5642-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC642-2C (6GK5642-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE SC646-2C (6GK5646-2GS00-2AC2): All versions prior to V2.3
  • SCALANCE SC646-2C (6GK5646-2GS00-2AC2) (only affected by CVE-2022-34821, CVE-2022-46142, CVE-2022-46143, CVE-2022-46144): All versions V2.3 and later, but prior to V3.0
  • SCALANCE W1748-1 M12 (6GK5748-1GY01-0TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W1748-1 M12 (6GK5748-1GY01-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W1788-1 M12 (6GK5788-1GY01-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W1788-2 EEC M12 (6GK5788-2GY01-0TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W1788-2 M12 (6GK5788-2GY01-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W1788-2IA M12 (6GK5788-2HY01-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W721-1 RJ45 (6GK5721-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W721-1 RJ45 (6GK5721-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W722-1 RJ45 (6GK5722-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W722-1 RJ45 (6GK5722-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W722-1 RJ45 (6GK5722-1FC00-0AC0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W734-1 RJ45 (6GK5734-1FX00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W734-1 RJ45 (6GK5734-1FX00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W734-1 RJ45 (6GK5734-1FX00-0AA6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W734-1 RJ45 (USA) (6GK5734-1FX00-0AB6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W738-1 M12 (6GK5738-1GY00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W738-1 M12 (6GK5738-1GY00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W748-1 M12 (6GK5748-1GD00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W748-1 M12 (6GK5748-1GD00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W748-1 RJ45 (6GK5748-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W748-1 RJ45 (6GK5748-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W761-1 RJ45 (6GK5761-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W761-1 RJ45 (6GK5761-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 M12 EEC (6GK5774-1FY00-0TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 M12 EEC (6GK5774-1FY00-0TB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 RJ45 (6GK5774-1FX00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 RJ45 (6GK5774-1FX00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 RJ45 (6GK5774-1FX00-0AC0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 RJ45 (6GK5774-1FX00-0AA6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W774-1 RJ45 (USA) (6GK5774-1FX00-0AB6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W778-1 M12 (6GK5778-1GY00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W778-1 M12 (6GK5778-1GY00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W778-1 M12 EEC (6GK5778-1GY00-0TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W778-1 M12 EEC (USA) (6GK5778-1GY00-0TB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-1 RJ45 (6GK5786-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-1 RJ45 (6GK5786-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2 RJ45 (6GK5786-2FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2 RJ45 (6GK5786-2FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2 RJ45 (6GK5786-2FC00-0AC0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2 SFP (6GK5786-2FE00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2 SFP (6GK5786-2FE00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2IA RJ45 (6GK5786-2HC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W786-2IA RJ45 (6GK5786-2HC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-1 M12 (6GK5788-1GD00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-1 M12 (6GK5788-1GD00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-1 RJ45 (6GK5788-1FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-1 RJ45 (6GK5788-1FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 M12 (6GK5788-2GD00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 M12 (6GK5788-2GD00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 M12 EEC (6GK5788-2GD00-0TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 M12 EEC (6GK5788-2GD00-0TB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 M12 EEC (6GK5788-2GD00-0TC0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 RJ45 (6GK5788-2FC00-0AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 RJ45 (6GK5788-2FC00-0AB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE W788-2 RJ45 (6GK5788-2FC00-0AC0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM763-1 (6GK5763-1AL00-7DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 (6GK5766-1GE00-7DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 (6GK5766-1GE00-7DB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 6GHz (6GK5766-1JE00-7DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 EEC (6GK5766-1GE00-7TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 EEC (6GK5766-1GE00-7TB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WAM766-1 EEC 6GHz (6GK5766-1JE00-7TA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WUM763-1 (6GK5763-1AL00-3DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WUM763-1 (6GK5763-1AL00-3AA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WUM766-1 (6GK5766-1GE00-3DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WUM766-1 (6GK5766-1GE00-3DB0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE WUM766-1 6GHz (6GK5766-1JE00-3DA0) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3 (SC, PN) (6GK5205-3BB00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3 (ST, E/IP) (6GK5205-3BD00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3 (ST, E/IP) (6GK5205-3BB00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3 (ST, PN) (6GK5205-3BD00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3LD (SC, E/IP) (6GK5205-3BF00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB205-3LD (SC, PN) (6GK5205-3BF00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB208 (E/IP) (6GK5208-0BA00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB208 (PN) (6GK5208-0BA00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3 (SC, E/IP) (6GK5213-3BD00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3 (SC, PN) (6GK5213-3BD00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3 (ST, E/IP) (6GK5213-3BB00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3 (ST, PN) (6GK5213-3BB00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3LD (SC, E/IP) (6GK5213-3BF00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB213-3LD (SC, PN) (6GK5213-3BF00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB216 (E/IP) (6GK5216-0BA00-2TB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XB216 (PN) (6GK5216-0BA00-2AB2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2 (SC) (6GK5206-2BD00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2 (ST/BFOC) (6GK5206-2BB00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2G PoE (6GK5206-2RS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2G PoE (54 V DC) (6GK5206-2RS00-5AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2G PoE EEC (54 V DC) (6GK5206-2RS00-5FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2SFP (6GK5206-2BS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2SFP EEC (6GK5206-2BS00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2SFP G (6GK5206-2GS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2SFP G (EIP DEF.) (6GK5206-2GS00-2TC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC206-2SFP G EEC (6GK5206-2GS00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208 (6GK5208-0BA00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208EEC (6GK5208-0BA00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208G (6GK5208-0GA00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208G (EIP def.) (6GK5208-0GA00-2TC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208G EEC (6GK5208-0GA00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208G PoE (6GK5208-0RA00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC208G PoE (54 V DC) (6GK5208-0RA00-5AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216 (6GK5216-0BA00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-3G PoE (6GK5216-3RS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-3G PoE (54 V DC) (6GK5216-3RS00-5AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-4C (6GK5216-4BS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-4C G (6GK5216-4GS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-4C G (EIP Def.) (6GK5216-4GS00-2TC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216-4C G EEC (6GK5216-4GS00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC216EEC (6GK5216-0BA00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC224 (6GK5224-0BA00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC224-4C G (6GK5224-4GS00-2AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC224-4C G (EIP Def.) (6GK5224-4GS00-2TC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XC224-4C G EEC (6GK5224-4GS00-2FC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XF204 (6GK5204-0BA00-2GF2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XF204 DNA (6GK5204-0BA00-2YF2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XF204-2BA (6GK5204-2AA00-2GF2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XF204-2BA DNA (6GK5204-2AA00-2YF2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM408-4C (6GK5408-4GP00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM408-4C (L3 int.) (6GK5408-4GQ00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM408-8C (6GK5408-8GS00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM408-8C (L3 int.) (6GK5408-8GR00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM416-4C (6GK5416-4GS00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XM416-4C (L3 int.) (6GK5416-4GR00-2AM2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP208 (6GK5208-0HA00-2AS6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP208 (Ethernet/IP) (6GK5208-0HA00-2TS6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP208EEC (6GK5208-0HA00-2ES6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP208PoE EEC (6GK5208-0UA00-5ES6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP216 (6GK5216-0HA00-2AS6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP216 (Ethernet/IP) (6GK5216-0HA00-2TS6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP216EEC (6GK5216-0HA00-2ES6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XP216POE EEC (6GK5216-0UA00-5ES6) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR324WG (24 x FE, AC 230V) (6GK5324-0BA00-3AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR324WG (24 X FE, DC 24V) (6GK5324-0BA00-2AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR326-2C PoE WG (6GK5326-2QS00-3AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR326-2C PoE WG (without UL) (6GK5326-2QS00-3RR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (24XFE, 4XGE, 24V) (6GK5328-4FS00-2AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (24xFE, 4xGE,DC24V) (6GK5328-4FS00-2RR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (24xFE,4xGE,AC230V) (6GK5328-4FS00-3AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (24xFE,4xGE,AC230V) (6GK5328-4FS00-3RR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (28xGE, AC 230V) (6GK5328-4SS00-3AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR328-4C WG (28xGE, DC 24V) (6GK5328-4SS00-2AR3) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 1x230V (6GK5524-8GS00-3AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 1x230V (L3 int.) (6GK5524-8GR00-3AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 24V (6GK5524-8GS00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 24V (L3 int.) (6GK5524-8GR00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 2x230V (6GK5524-8GS00-4AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR524-8C, 2x230V (L3 int.) (6GK5524-8GR00-4AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 1x230V (6GK5526-8GS00-3AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 1x230V (L3 int.) (6GK5526-8GR00-3AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 24V (6GK5526-8GS00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 24V (L3 int.) (6GK5526-8GR00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 2x230V (6GK5526-8GS00-4AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR526-8C, 2x230V (L3 int.) (6GK5526-8GR00-4AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR528-6M (6GK5528-0AA00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR528-6M (2HR2, L3 int.) (6GK5528-0AR00-2HR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR528-6M (2HR2) (6GK5528-0AA00-2HR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR528-6M (L3 int.) (6GK5528-0AR00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR552-12M (6GK5552-0AA00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR552-12M (2HR2, L3 int.) (6GK5552-0AR00-2AR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR552-12M (2HR2) (6GK5552-0AA00-2HR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SCALANCE XR552-12M (2HR2) (6GK5552-0AR00-2HR2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SIPLUS NET SCALANCE XC206-2 (6AG1206-2BB00-7AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SIPLUS NET SCALANCE XC206-2SFP (6AG1206-2BS00-7AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SIPLUS NET SCALANCE XC208 (6AG1208-0BA00-7AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions
  • SIPLUS NET SCALANCE XC216-4C (6AG1216-4BS00-7AC2) (only affected by CVE-2022-46140, CVE-2022-46142, CVE-2022-46143): All versions

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER CONTROL OF GENERATION OF CODE ('CODE INJECTION') CWE-94

By injecting code into specific configuration options for OpenVPN, an attacker could execute arbitrary code with elevated privileges on affected Siemens RUGGEDCOM and SCALANCE devices.

CVE-2022-34821 has been assigned to this vulnerability. A CVSS v3 base score of 7.6 has been calculated. the CVSS vector string is (CVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H)

3.2.2    USE OF A BROKEN OR RISKY CRYPTOGRAPHIC ALGORITHM CWE-327

Affected Siemens RUGGEDCOM and SCALANCE devices use a weak encryption scheme to encrypt the debug zip file. This could allow an authenticated attacker to decrypt the contents of the file and retrieve debug information about the system.

CVE-2022-46140 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated. the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N)

3.2.3    STORING PASSWORDS IN A RECOVERABLE FORMAT CWE-257

Affected Siemens RUGGEDCOM and SCALANCE devices store command line interface (CLI) user passwords encrypted in flash memory. Attackers with physical access to the device could retrieve the file and decrypt CLI user passwords.

CVE-2022-46142 has been assigned to this vulnerability. A CVSS v3 base score of 5.7 has been calculated. the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L)

3.2.4    IMPROPER VALIDATION OF SPECIFIED QUANTITY IN INPUT CWE-1284

Affected Siemens RUGGEDCOM and SCALANCE devices do not check the TFTP blocksize correctly. This could allow an authenticated attacker to read from an uninitialized buffer potentially containing previously allocated data.

CVE-2022-46143 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been calculated. the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:N/A:N)

3.2.5    IMPROPER CONTROL OF A RESOURCE THROUGH ITS LIFETIME CWE-664

Affected Siemens SCALANCE devices do not properly process CLI commands after a user forcefully quits the secure shell (SSH) connection. This could allow an authenticated attacker to make the CLI via SSH or serial interface irresponsive.

CVE-2022-46144 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated. the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H)

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide 
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends updating to the latest version of its software where available:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage 

For more information, see the associated Siemens security advisory SSA-413565 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolate them from business networks.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Siemens