Delta Electronics DIAEnergie
1. EXECUTIVE SUMMARY
- CVSS v3 8.8
- ATTENTION: Exploitable remotely
- Vendor: Delta Electronics
- Equipment: DIAEnergie
- Vulnerabilities: Improper Authorization, SQL Injection, Path Traversal, Cross-site Scripting
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to escalate privileges, disclose sensitive information, or disrupt system availability.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Delta Electronics products are affected:
- DIAEnergie: Versions prior to v1.10.00.005.
3.2 Vulnerability Overview
3.2.1 IMPROPER AUTHORIZATION CWE-285
Privileges are not fully verified server-side, which can be abused by a user with limited privileges to bypass authorization and access privileged functionality.
CVE-2024-28029 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H.
3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in the script Handler_CFG.ashx.
CVE-2024-28891 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.3 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in the script DIAE_tagHandler.ashx.
CVE-2024-25937 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.4 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in GetDIAE_astListParameters.
CVE-2024-28040 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.5 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in GetDIAE_slogListParameters.
CVE-2024-23975 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.6 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in GetDIAE_unListParameters.
CVE-2024-23494 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.7 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89
SQL injection vulnerability exists in GetDIAE_usListParameters.
CVE-2024-25574 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.8 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22
It is possible to perform a path traversal attack and write outside of the intended directory. If a file name is specified that already exists on the file system, then the original file will be overwritten.
CVE-2024-28171 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H).
3.2.9 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22
Path traversal attack is possible and write outside of the intended directory and may access sensitive information. If a file name is specified that already exists on the file system, then the original file will be overwritten.
CVE-2024-25567 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H).
3.2.10 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79
Improper Neutralization of Input within the affected product could lead to cross-site Scripting.
CVE-2024-28045 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:U/C:L/I:L/A:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Taiwan
3.4 RESEARCHER
Michael Heinzl reported these vulnerabilities to CISA.
4. MITIGATIONS
Delta recommends users update to DIAEnergie v1.10.00.005. Users can request this version of DIAEnergie from Delta Electronics' regional sales or agents.
CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- March 14, 2024: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Delta Electronics