Mitsubishi Electric Multiple FA Engineering Software Products (Update D)
1. EXECUTIVE SUMMARY
- CVSS v4 4.4
- ATTENTION: Low attack complexity
- Vendor: Mitsubishi Electric
- Equipment: Multiple FA Engineering Software Products
- Vulnerabilities: Improper Privilege Management, Uncontrolled Resource Consumption, Out-of-bounds Write
2. RISK EVALUATION
Successful exploitation of these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition. Additionally, an attacker may gain Windows system privileges and execute arbitrary commands.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Mitsubishi Electric reports the following versions of FA Engineering Software Products are affected:
- CPU Module Logging Configuration Tool: Version "1.154L" and prior
- CSGL (GX Works2 connection configuration): Version "2.5" and prior
- CW Configurator: Version "1.019V" and prior
- Data Transfer: Version "3.58L" and prior
- Data Transfer Classic: Version "1.00A" and prior
- EZSocket (communication middleware product for Mitsubishi Electric partner companies): Version "5.92" and prior
- FR Configurator SW3: All versions
- FR Configurator2: Version "1.32J" and prior
- GENESIS64: All versions
- GT Designer3 Version1 (GOT1000): Version "1.310Y" and prior
- GT Designer3 Version1 (GOT2000): Version "1.317F" and prior
- GT SoftGOT1000 Version3: Version "3.310Y" and prior
- GT SoftGOT2000 Version1: Version "1.315D" and prior
- GX Developer: All versions
- GX LogViewer: Version "1.154L" and prior
- GX Works2: Version "1.622Y" and prior
- GX Works3: Version "1.106L" and prior
- iQ Works (MELSOFT Navigator): Version "2.102G" and prior
- MI Configurator: All versions
- Mitsubishi Electric Numerical Control Device Communication Software (FCSB1224): All versions
- MR Configurator (SETUP221): All versions
- MR Configurator2: Version "1.150G" and prior
- Position Board Utility2 (MRZJW3-MC2-UTL): Version "3.40" and prior
- MX Component: Version "5.007H" and prior
- MX OPC Server DA/UA (Software packaged with MC Works64): All versions
- PX Developer/Monitor Tool: All versions
- RT ToolBox3: Version "2.20W" and prior
- RT VisualBox: All versions
- Setting/monitoring tools for the C Controller module (SW4PVC-CCPU): Version "4.14Q" and prior
- MELSECNET/H Interface Board software package (SW0DNC-MNETH-B): Version "36N" and prior
- CC-Link System Master/Local Interface Board software package (SW1DNC-CCBD2-B): Version "1.25B" and prior
- CC-Link IE Field Network Interface Board software package (SW1DNC-CCIEF-J): Version "1.18U" and prior
- CC-Link IE Field Network Interface Board software package (SW1DNC-CCIEF-B): Version "1.18U" and prior
- CC-Link IE Controller Network Interface Board software package (SW1DNC-MNETG-B): Version "1.31H" and prior
- C Controller Interface Module utility (SW1DNC-QSCCF-B): All versions
- MELSOFT EM Software Development Kit (SW1DND-EMSDK-B): Version "1.020W" and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 Improper Privilege Management CWE-269
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to gain Windows system privileges and execute arbitrary commands.
CVE-2023-51776 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2023-51776. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.2 Uncontrolled Resource Consumption CWE-400
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2023-51777 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2023-51777. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.3 Out-of-bounds Write CWE-787
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2023-51778 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2023-51778. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.4 Uncontrolled Resource Consumption CWE-400
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2024-22102 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2024-22102. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.5 Out-of-bounds Write CWE-787
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2024-22103 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2024-22103. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.6 Out-of-bounds Write CWE-787
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2024-22104 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2024-22104. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.7 Uncontrolled Resource Consumption CWE-400
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2024-22105 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2024-22105. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.8 Improper Privilege Management CWE-269
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition. Additionally, an attacker may gain Windows system privileges and execute arbitrary commands.
CVE-2024-22106 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-22106. A base score of 4.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.9 Improper Privilege Management CWE-269
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to gain Windows system privileges and execute arbitrary commands.
CVE-2024-25086 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-25086. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.10 Uncontrolled Resource Consumption CWE-400
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to cause a Windows blue screen error that results in a denial-of-service condition.
CVE-2024-25087 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2024-25087. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.11 Improper Privilege Management CWE-269
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to gain Windows system privileges and execute arbitrary commands.
CVE-2024-25088 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-25088. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.12 Improper Privilege Management CWE-269
If a malicious code is executed on a computer where the affected software product is installed, these vulnerabilities may allow a local attacker to gain Windows system privileges and execute arbitrary commands.
CVE-2024-26314 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-26314. A base score of 4.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Japan
3.4 RESEARCHER
Jongseong Kim, Byunghyun Kang, Sangjun Park, Yunjin Park, Kwon Yul, and Seungchan Kim reported these vulnerabilities to Mitsubishi Electric.
4. MITIGATIONS
Mitsubishi Electric recommends users download and install the update as follows:
- CPU Module Logging Configuration Tool : Update to"1.160S" or later.
- CSGL (GX Works2 connection configuration): Update to "2.6" or later - contact your place of purchase for assistance.
- CW Configurator: Update to "1.020W" or later
- Data Transfer: Update to "3.59M" or later.
- Data Transfer Classic: Update to "1.01B" or later.
- EZSocket: Update to "5.A" or later - contact your place of purchase for assistance.
- FR Configurator2: Update to "1.33K" or later.
- GT Designer3 Version1 (GOT1000): Update to "1.315D" or later.
- GT Designer3 Version1 (GOT2000): Update to "1.320J" or later.
- GT SoftGOT1000 Version3: Update to "3.315D" or later.
- GT SoftGOT2000 Version1: Update to "1.320J" or later.
- GX LogViewer: Update to "1.160S" or later.
- GX Works2: Update to "1.625B" or later.
- GX Works3: Update to "1.110Q" or later.
- iQ Works (MELSOFT Navigator): Update to "2.106L" or later.
- MR Configurator2: Update to "1.155M" or later
- MX Component: Update to "5.008J" or later.
- Position Board Utility2(MRZJW3-MC2-UTL): Update to "3.50" or later.
- RT ToolBox3: Update to "2.50C" or later.
- Setting/monitoring tools for the C Controller module (SW4PVC-CCPU): Update to "4.15R" or later
- MELSECNET/H Interface Board software package (SW0DNC-MNETH-B): Update to "37P" or later.
- CC-Link System Master/Local Interface Board software package (SW1DNC-CCBD2-B): Update to "1.26C" or later.
- CC-Link IE Field Network Interface Board software package (SW1DNC-CCIEF-J/-B): Update to "1.19V" or later.
- CC-Link IE Controller Network Interface Board software package (SW1DNC-MNETG-B): Update to "1.32J" or later.
- MELSOFT EM Software Development Kit (SW1DND-EMSDK-B): Update to "1.025B" or later
Mitsubishi Electric recommends users take the following mitigation measures to minimize the risk of exploiting these vulnerabilities:
- Restrict physical access to the computer using the product.
- Install an antivirus software in your computer using the affected product.
- Don't open untrusted files or click untrusted links.
For additional information see Mitsubishi Electric advisory 2024-001.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY
- May 14, 2024: Initial Republication of Mitsubishi Electric 2024-001
- October 31, 2024: Update A - added version information to affected product and mitigation sections.
- January 30, 2025: Update B - added version information to affected product and mitigation sections.
- May 15, 2025: Update C - added version information for Position Board Utility2
- August 28, 2025: Update D - added version information to affected product and mitigation sections.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Mitsubishi Electric