Siemens SIMATIC WinCC
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY
- CVSS v4 8.2
- ATTENTION: Exploitable remotely
- Vendor: Siemens
- Equipment: SIMATIC WinCC
- Vulnerability: Exposure of Private Personal Information to an Unauthorized Actor
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to retrieve information such as users and passwords.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following versions of SIMATIC WinCC are affected:
- Siemens SIMATIC PCS 7 V9.1: all versions
- Siemens SIMATIC WinCC Runtime Professional V18: all versions
- Siemens SIMATIC WinCC Runtime Professional V19: all versions
- Siemens SIMATIC WinCC V7.4: versions prior to V7.4 SP1 Update 23
- Siemens SIMATIC WinCC V7.5: versions prior to V7.5 SP2 Update 17
- Siemens SIMATIC WinCC V8.0: versions prior to V8.0 Update 5
3.2 Vulnerability Overview
3.2.1 EXPOSURE OF PRIVATE PERSONAL INFORMATION TO AN UNAUTHORIZED ACTOR CWE-359
The affected products do not properly handle certain requests to their web application, which may lead to the leak of privileged information. This could allow an unauthenticated remote attacker to retrieve information such as users and passwords.
CVE-2024-30321 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-30321. A base score of 8.2 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has released new versions for several affected products and recommends updating to the latest versions. Siemens is preparing further fix versions and recommends countermeasures for products where fixes are not, or not yet available.
- SIMATIC PCS 7 V9.1: Update WinCC to V7.5 SP2 Update 17 or later version
- SIMATIC WinCC V7.4: Update to V7.4 SP1 Update 23 or later version
- SIMATIC WinCC V7.5: Update to V7.5 SP2 Update 17 or later version
- SIMATIC WinCC V8.0: Update to V8.0 Update 5 or later version
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- Restrict access to application webserver for trusted users only
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-883918 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.
5. UPDATE HISTORY
- July 11, 2024: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Siemens