As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: Siemens Engineering Platforms
  • Vulnerability: Improper Input Validation

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to execute arbitrary commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SIMATIC STEP 7 Safety V18: All versions
  • Siemens SIMATIC STEP 7 Safety V19: All versions
  • Siemens SIMATIC S7-PLCSIM V18: All versions
  • Siemens SIMOCODE ES V18: All versions
  • Siemens SIMATIC WinCC Unified V17: All versions
  • Siemens SINAMICS Startdrive V18: All versions
  • Siemens SIMATIC STEP 7 V17: All versions
  • Siemens SIMATIC WinCC V19: All versions
  • Siemens SIRIUS Safety ES V17 (TIA Portal): All versions
  • Siemens TIA Portal Cloud V19: All versions
  • Siemens SIRIUS Safety ES V18 (TIA Portal): All versions
  • Siemens SIMATIC STEP 7 V19: All versions
  • Siemens SIRIUS Soft Starter ES V18 (TIA Portal): All versions
  • Siemens SIRIUS Safety ES V19 (TIA Portal): All versions
  • Siemens SIMOTION SCOUT TIA V5.4 SP3: All versions
  • Siemens SIMOTION SCOUT TIA V5.5 SP1: All versions
  • Siemens SINAMICS Startdrive V17: All versions
  • Siemens TIA Portal Cloud V17: All versions
  • Siemens SIMOCODE ES V17: All versions
  • Siemens SIMATIC STEP 7 Safety V17: All versions
  • Siemens SIRIUS Soft Starter ES V19 (TIA Portal): All versions
  • Siemens SIMATIC WinCC Unified PC Runtime V19: All versions
  • Siemens SIMATIC WinCC V18: All versions
  • Siemens SIMATIC WinCC Unified PC Runtime V18: All versions
  • Siemens SINAMICS Startdrive V19: All versions
  • Siemens SIRIUS Soft Starter ES V17 (TIA Portal): All versions
  • Siemens SIMOTION SCOUT TIA V5.6 SP1: All versions
  • Siemens SIMATIC WinCC Unified V18: All versions
  • Siemens SIMATIC WinCC V17: All versions
  • Siemens TIA Portal Cloud V18: All versions
  • Siemens SIMATIC STEP 7 V18: All versions
  • Siemens SIMATIC WinCC Unified V19: All versions
  • Siemens SIMOCODE ES V19: All versions
  • Siemens SIMATIC S7-PLCSIM V17: All versions

3.2 Vulnerability Overview

3.2.1 IMPROPER INPUT VALIDATION CWE-20

The affected devices do not properly sanitize user-controllable input when parsing user settings. This could allow an attacker to locally execute arbitrary commands in the host operating system with the privileges of the user.

CVE-2024-52051 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-52051. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Currently no fix is available

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-392859 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • December 12, 2024: Initial Publication