Johnson Controls Software House C●CURE 9000 (Update A)
1. EXECUTIVE SUMMARY
- CVSS v4 8.5
- ATTENTION: Exploitable remotely/Low attack complexity
- Vendor: Johnson Controls Inc.
- Equipment: Software House C●CURE 9000
- Vulnerability: Incorrect Default Permissions
2. RISK EVALUATION
Successful exploitation of this vulnerability may allow an attacker to access credentials used for access to the application.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following Johnson Controls Inc. products are affected when the optional C•CURE IQ Web and/or C•CURE Portal is installed:
- Software House C●CURE 9000 Site Server: Version 3.00.3 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 INCORRECT DEFAULT PERMISSIONS CWE-276
Under certain circumstances the Software House C●CURE 9000 Site Server provides insufficient protection of directories containing executables.
CVE-2024-32861 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) ).
A CVSS v4 score has also been calculated for CVE-2024-32861. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Commercial Facilities, Government Facilities, Transportation Systems, Energy
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Ireland
3.4 RESEARCHER
Reid Wightman of Dragos reported this vulnerability to Johnson Controls, Inc.
4. MITIGATIONS
Johnson Controls, Inc. recommends the following:
- Remove Full control and Write permissions.
- For non-administrator accounts, limit permissions to Read & Execute on the following path: C:\CouchDB\bin
- For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2024-11 v2 at the following location: https://www.johnsoncontrols.com/cyber-solutions/security-advisories
- Aligning with CISA recommendations, Johnson Controls recommends taking steps to minimize risks to all building automation systems.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- July 9, 2024: Initial Publication
- January 16, 2025: Update A - Update to affected products, updated mitigations.
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Johnson Controls Inc.