Siemens SIMATIC STEP 7 (TIA Portal)
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY
- CVSS v4 8.5
- ATTENTION: Low attack complexity
- Vendor: Siemens
- Equipment: SIMATIC STEP 7 (TIA Portal)
- Vulnerability: Deserialization of Untrusted Data
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:
- SIMATIC PCS neo V4.0: all versions
- SIMATIC STEP 7 V16: all versions
- SIMATIC STEP 7 V17: all versions
- SIMATIC STEP 7 V18: versions prior to V18 Update 2
3.2 Vulnerability Overview
3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502
Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300.
CVE-2022-45147 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2022-45147. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has released a new version for SIMATIC STEP 7 (TIA Portal) V18 and recommends updating to the latest version. Siemens recommends specific countermeasures for products where fixes are not, or not yet available:
- SIMATIC STEP 7 V18: Update to V18 Update 2 or later version
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- Avoid opening untrusted files from unknown sources in affected products
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-825651 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.
5. UPDATE HISTORY
- July 11, 2024: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor