ABB Low Voltage DC Drives and Power Controllers CODESYS RTS
1. EXECUTIVE SUMMARY
- CVSS v3 8.8
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: ABB
- Equipment: DCT880 memory unit incl. ABB Drive Application Builder license (IEC 61131-3), DCT880 memory unit incl. Power Optimizer, DCS880 memory unit incl. ABB Drive Application Builder license (IEC 61131-3), DCS880 memory unit incl. DEMag, DCS880 memory unit incl. DCC
- Vulnerabilities: Improper Input Validation, Out-of-bounds Write, Improper Restriction of Operations within the Bounds of a Memory Buffer
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow attackers to trigger a denial-of-service condition or execute arbitrary code over the fieldbus interfaces.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
ABB reports that the following low-voltage DC drive and power controller products contain a vulnerable version of the CODESYS Runtime:
- DCT880 memory unit incl. ABB Drive Application Builder license (IEC 61131-3): All versions
- DCT880 memory unit incl. Power Optimizer: All versions
- DCS880 memory unit incl. ABB Drive Application Builder license (IEC 61131-3): All versions
- DCS880 memory unit incl. DEMag: All versions
- DCS880 memory unit incl. DCC: All versions
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER INPUT VALIDATION CWE-20
After successful authentication as a user in multiple versions of multiple CODESYS products, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37559 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.2 IMPROPER INPUT VALIDATION CWE-20
After successful authentication as a user in multiple versions of multiple CODESYS products, specific crafted network communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37558 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.3 OUT-OF-BOUNDS WRITE CWE-787
After successful authentication as a user in multiple versions of multiple CODESYS products, specific crafted remote communication requests can cause the CmpAppBP component to overwrite a heap-based buffer which can lead to a denial-of-service condition
CVE-2023-37557 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.4 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37556 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.5 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37555 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.6 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37554 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.7 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37553 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.8 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37552 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.9 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37550 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.10 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37549 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.11 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37548 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.12 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37547 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.13 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37546 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.14 IMPROPER INPUT VALIDATION CWE-20
In multiple versions of multiple CODESYS products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-of-service condition.
CVE-2023-37545 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.15 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119
In multiple versions of CODESYS Control an improper restriction of operations within the bounds of a memory buffer allow a remote attacker with user privileges to gain full access of the device.
CVE-2022-4046 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Switzerland
3.4 RESEARCHER
ABB PSIRT reported these vulnerabilities to CISA.
4. MITIGATIONS
If the drive or power controller is in an exploitable configuration, ABB recommends immediately applying the mitigations described in the workarounds section of the ABB security advisory.
For more information, see ABB's security advisory.
ABB strongly recommends the following (non-exhaustive) list of general cyber security practices for any installation of software-related products:
- Isolate special purpose networks (e.g. for automation systems) and remote devices behind firewalls and separate them from any general-purpose network (e.g. office or home networks).
- Install physical controls so no unauthorized personnel can access your devices, components, peripheral equipment, and networks.
- Minimize network exposure for all applications and endpoints to ensure that they are not accessible from the Internet unless they are designed for such exposure and the intended use requires such.
- Ensure all nodes are always up to date in terms of installed software, operating system, and firmware patches as well as anti-virus and firewall.
- When remote access is required, use secure methods, such as virtual private networks (VPNs). Also, understand that VPNs are only as secure as the connected devices.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- April 3, 2025: Initial Republication of ABB 9AKK108470A9494