Siemens Teamcenter Visualization and JT2Go
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY
- CVSS v4 7.3
- ATTENTION: Low Attack Complexity
- Vendor: Siemens
- Equipment: Teamcenter Visualization and JT2Go
- Vulnerabilities: Out-of-bounds Read, NULL Pointer Dereference
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to execute code in the context of the current process and crash the application causing denial of service condition.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Siemens Teamcenter Visualization and JT2Go, are affected:
- Siemens JT2Go: Versions prior to V2312.0005
- Siemens Teamcenter Visualization V14.2: Versions prior to V14.2.0.12
- Siemens Teamcenter Visualization V14.3: Versions prior to V14.3.0.10
- Siemens Teamcenter Visualization V2312: Versions prior to V2312.0005
3.2 Vulnerability Overview
3.2.1 OUT-OF-BOUNDS READ CWE-125
The affected applications contain an out of bounds read past the unmapped memory region while parsing specially crafted X_T files. This could allow an attacker to execute code in the context of the current process.
CVE-2024-32635 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-32635. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 OUT-OF-BOUNDS READ CWE-125
The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted X_T files. This could allow an attacker to execute code in the context of the current process.
CVE-2024-32636 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-32636. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 NULL POINTER DEREFERENCE CWE-476
The affected applications contain a null pointer dereference vulnerability while parsing specially crafted X_T files. An attacker could leverage this vulnerability to crash the application causing denial of service condition.
CVE-2024-32637 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).
A CVSS v4 score has also been calculated for CVE-2024-0056. A base score of 4.8 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, and Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Jin Huang from ADLab of Venustech reported these vulnerabilities to Siemens.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- All affected products: Do not open untrusted X_T files in affected applications
- Teamcenter Visualization V14.2: Update to V14.2.0.12 or later version
- Teamcenter Visualization V14.3: Update to V14.3.0.10 or later version
- JT2Go: Update to V2312.0005 or later version
- Teamcenter Visualization V2312: Update to V2312.0005 or later version
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-856475 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY
- August 15, 2024: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Siemens