Fuji Electric Tellus Lite V-Simulator
1. EXECUTIVE SUMMARY
- CVSS v4 8.4
- ATTENTION: Low attack complexity
- Vendor: Fuji Electric
- Equipment: Tellus Lite V-Simulator
- Vulnerabilities: Out-of-bounds Write
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could crash the device being accessed.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
VS5Sim is a simulator of V-SFT Ver5 packaged with Fuji Electric Tellus Lite V-Simulator, a remote monitoring and operation software. The following versions are affected:
- Tellus Lite: Version 4.0.20.0
3.2 Vulnerability Overview
3.2.1 Out-of-bounds Write CWE-787
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Fuji Electric Tellus Lite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of V8 files in the V-Simulator 5 component. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of the current process.
CVE-2024-11799 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-11799. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 Out-of-bounds Write CWE-787
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Fuji Electric Tellus Lite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of V8 files in the V-Simulator 5 component. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of the current process.
CVE-2024-11800 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-11800. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 Out-of-bounds Write CWE-787
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Fuji Electric Tellus Lite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of V8 files in the V-Simulator 5 component. The issue results from the lack of proper validation of user-supplied data, which can result in a write past the end of an allocated data structure. An attacker can leverage this vulnerability to execute code in the context of the current process.
CVE-2024-11801 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-11801. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.4 Out-of-bounds Write CWE-787
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Fuji Electric Tellus Lite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of V8 files in the V-Simulator 5 component. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of the current process.
CVE-2024-11802 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-11802. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.5 Out-of-bounds Write CWE-787
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Fuji Electric Tellus Lite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of V8 files in the V-Simulator 5 component. The issue results from the lack of proper validation of user-supplied data, which can result in a write past the end of an allocated data structure. An attacker can leverage this vulnerability to execute code in the context of the current process.
CVE-2024-11803 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-11803. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Japan
3.4 RESEARCHER
kimiya working with Trend Micro Zero Day Initiative reported these vulnerabilities to CISA.
4. MITIGATIONS
VS5Sim is a simulator of V-SFT Ver5 packaged with TELLUS Lite. VS6Sim screens incoming data to prevent malicious files from exploiting these vulnerabilities. Fuji Electric has replaced V-SFT Ver5 with V-SFT Ver6 in new versions of TELLUS lite.
Fuji Electric plans a fix for CVE-2024-11802 and CVE-2024-11803 in May 2025.
CISA recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities have been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY
- December 3, 2024: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Fuji Electric