Siemens SIMATIC PCS neo and TIA Administrator
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
1. EXECUTIVE SUMMARY
- CVSS v4 8.7
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Siemens
- Equipment: SIMATIC PCS neo and TIA Administrator
- Vulnerability: Insufficient Session Expiration
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow a remote unauthenticated attacker, who has obtained the session token by other means, to re-use a legitimate user's session even after logout.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:
- SIMOCODE ES V19: Versions prior to V19 Update 1
- TIA Administrator: Versions 3.0.4 and prior
- SIMATIC PCS neo V4.1: Versions prior to V4.1 Update 2
- SIMATIC PCS neo V4.0: All versions
- SIRIUS Safety ES V19 (TIA Portal): Versions prior to V19 Update 1
- SIRIUS Soft Starter ES V19 (TIA Portal): Versions prior to V19 Update 1
- SIMATIC PCS neo V5.0: Versions prior to V5.0 Update 1
3.2 VULNERABILITY OVERVIEW
3.2.1 INSUFFICIENT SESSION EXPIRATION CWE-613
Affected products do not correctly invalidate user sessions upon user logout. This could allow a remote unauthenticated attacker, who has obtained the session token by other means, to re-use a legitimate user's session even after logout.
CVE-2024-45386 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-45386. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:
- Close browser and client after logout and remove all locally stored session tokens
- SIMATIC PCS neo V4.0: Currently no fix is planned
- SIMOCODE ES V19: Update to V19 Update 1 or later version
- SIRIUS Soft Starter ES V19 (TIA Portal): Update to V19 Update 1 or later version
- SIRIUS Safety ES V19 (TIA Portal): Update to V19 Update 1 or later version
- TIA Administrator: Update to V3.0.4 or later version
- SIMATIC PCS neo V4.1: Update to V4.1 Update 2 or later version
- SIMATIC PCS neo V5.0: Update to V5.0 Update 1 or later version
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-342348 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY
- February 13, 2025: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Siemens