mySCADA myPRO Manager
1. EXECUTIVE SUMMARY
- CVSS v4 10.0
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: mySCADA
- Equipment: myPRO Manager
- Vulnerabilities: OS Command Injection, Missing Authentication for Critical Function, Cleartext Storage of Sensitive Information, Cross-Site Request Forgery (CSRF)
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary OS commands, upload files, and obtain sensitive information without providing associated credentials.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following mySCADA products are affected:
- myPRO Manager: Versions prior to 1.4
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS Command ('OS COMMAND INJECTION') CWE-78
The affected product is vulnerable to an OS command injection which could allow a remote attacker to execute arbitrary OS commands.
CVE-2025-25067 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-25067. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306
The administrative web interface can be accessed without authentication which could allow an unauthorized attacker to retrieve sensitive information and upload files without the associated password.
CVE-2025-24865 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-24865. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).
3.2.3 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312
The affected product stores credentials in cleartext, which could allow an attacker to obtain sensitive information.
CVE-2025-22896 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-22896. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:N/SA:N).
3.2.4 CROSS-SITE REQUEST FORGERY (CSRF) CWE-352
The affected product is vulnerable to cross-site request forgery (CSRF), which could allow an attacker to obtain sensitive information. An attacker would need to trick the victim in to visiting an attacker-controlled website.
CVE-2025-23411 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).
A CVSS v4 score has also been calculated for CVE-2025-23411. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Czech Republic
3.4 RESEARCHER
Michael Heinzl reported these vulnerabilities to CISA.
4. MITIGATIONS
mySCADA recommends users update to myPRO Manager v1.4
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- February 13, 2025: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- mySCADA