Schneider Electric Enerlin’X IFE and eIFE
1. EXECUTIVE SUMMARY
- CVSS v4 7.1
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Schneider Electric
- Equipment: Enerlin'X IFE interface and Enerlin'X eIFE
- Vulnerabilities: Improper Input Validation
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service condition which would require the device to need to be manually rebooted.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Enerlin'X IFE interface and Enerlin'X eIFE are affected:
- Enerlin'X IFE interface: All versions
- Enerlin'X eIFE: All versions
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER INPUT VALIDATION CWE-20
An improper input validation vulnerability exists that could cause a denial of service of the product when malicious IPV6 packets are sent to the device.
CVE-2025-0816 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-0816. A base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.2 IMPROPER INPUT VALIDATION CWE-20
An improper input validation vulnerability exists that could cause denial of service of the product when malicious ICMPV6 packets are sent to the device.
CVE-2025-0815 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-0815. A base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.3 IMPROPER INPUT VALIDATION CWE-20
An improper input validation vulnerability exists that could cause denial of service of the network services running on the product when malicious IEC61850-MMS packets are sent to the device. The core functionality of the breaker remains intact during the attack.
CVE-2025-0814 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
A CVSS v4 score has also been calculated for CVE-2025-0814. A base score of 6.9 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: France
3.4 RESEARCHER
Schneider Electric reported these vulnerabilities to CISA.
4. MITIGATIONS
Schneider Electric has identified the following specific remediations and mitigations users can apply to reduce risk:
- CVE-2025-0814: Version 004.010.000 of Enerlin'X IFE and eIFE includes a fix for this vulnerability. Download the latest version of the EcoStruxure Power Commission tool available to install the latest firmware version of the Enerlin'X IFE and eIFE.
Users should use appropriate patching methodologies when applying these patches to their systems. Schneider Electric strongly recommends the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric's Customer Care Center for assistance removing a patch.
If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:
Enerlin'X IFE and eIFE: All versions (CVE-2025-0815 and CVE-2025-0816).
Users should immediately apply the following mitigations to reduce the risk of exploit:
- Use devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public Internet or untrusted networks.
- Setup network segmentation and implement a firewall to block all unauthorized access to ports supported by the product and listed in the user guide.
- Configure the Access Control List following the recommendations of the Cybersecurity Guide and the user guide.
- To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric's security notification service.
Schneider Electric strongly recommends the following industry cybersecurity best practices:
- Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
- Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
- Place all controllers in locked cabinets and never leave them in the "Program" mode.
- Never connect programming software to any network other than the network intended for that device.
- Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
- Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
- Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For more information about these vulnerabilities, see Schneider Electric security notification "SEVD-2025-042-04 Enerlin'X IFE and eIFE".
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
- Do not click web links or open attachments in unsolicited email messages.
- Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
- Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY
- March 20, 2025: Initial Publication
This product is provided subject to this Notification and this Privacy & Use policy.
Vendor
- Schneider Electric