ICS Advisory

Rockwell Automation ControlLogix, GuardLogix, and CompactLogix

Release Date
Alert Code
ICSA-24-163-01

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.3
  • ATTENTION: Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: ControlLogix, GuardLogix, CompactLogix
  • Vulnerability: Always-Incorrect Control Flow Implementation

2. RISK EVALUATION

Successful exploitation of this vulnerability could compromise the availability of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports that the following controllers are affected:

  • ControlLogix 5580: V34.011
  • GuardLogix 5580: V34.011
  • 1756-EN4: V4.001
  • CompactLogix 5380: V34.011
  • Compact GuardLogix 5380: V34.011
  • CompactLogix 5480: V34.011

3.2 Vulnerability Overview

3.2.1 Always-Incorrect Control Flow Implementation CWE-670

Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault (MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.

CVE-2024-5659 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-5659. A base score of 8.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation offers users the following solutions:

  • ControlLogix 5580: corrected in V34.014, V35.013, V36.011 and later
  • GuardLogix 5580: corrected in V34.014, V35.013, V36.011 and later
  • 1756-EN4: corrected in V6.001 and later
  • CompactLogix 5380: corrected in V34.014, V35.013, V36.011 and later
  • Compact GuardLogix 5380: corrected in V34.014, V35.013, V36.011 and later
  • CompactLogix 5480: corrected in V34.014, V35.013, V36.011 and later

Rockwell Automation encourages users of the affected software, who are not able to upgrade to one of the corrected versions, to apply the risk mitigations where possible.

For more information, see Rockwell Automation's security advisory

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • June 11, 2024: Initial Publication

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

  • Rockwell Automation