Optigo Networks Visual BACnet Capture Tool/Optigo Visual Networks Capture Tool
1. EXECUTIVE SUMMARY
- CVSS v4 9.3
- ATTENTION: Exploitable remotely/low attack complexity
- Vendor: Optigo Networks
- Equipment: Visual BACnet Capture Tool, Optigo Visual Networks Capture Tool
- Vulnerabilities: Use of Hard-coded, Security-relevant Constants, Authentication Bypass Using an Alternate Path or Channel
2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to bypass authentication, gain control over the products, or impersonate the web applications.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Optigo Networks Visual BACnet Capture Tool and Optigo Visual Networks Capture Tool are affected:
- Visual BACnet Capture Tool: Version 3.1.2rc11
- Optigo Visual Networks Capture Tool: Version 3.1.2rc11
3.2 VULNERABILITY OVERVIEW
3.2.1 USE OF HARD-CODED, SECURITY-RELEVANT CONSTANTS CWE-547
Optigo Networks Visual BACnet Capture Tool and Optigo Visual Networks Capture Tool version 3.1.2rc11 contain a hard coded secret key. This could allow an attacker to generate valid JWT (JSON Web Token) sessions.
CVE-2025-2079 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-2079. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.2 AUTHENTICATION BYPASS USING AN ALTERNATE PATH OR CHANNEL CWE-288
Optigo Networks Visual BACnet Capture Tool and Optigo Visual Networks Capture Tool version 3.1.2rc11 contain an exposed web management service that could allow an attacker to bypass authentication measures and gain controls over utilities within the products.
CVE-2025-2080 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-2080. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 USE OF HARD-CODED, SECURITY-RELEVANT CONSTANTS CWE-547
Optigo Networks Visual BACnet Capture Tool and Optigo Visual Networks Capture Tool version 3.1.2rc11 are vulnerable to an attacker impersonating the web application service and mislead victim clients.
CVE-2025-2081 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-2081. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Information Technology
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Canada
3.4 RESEARCHER
Tomer Goldschmidt of Claroty Team82 reported these vulnerabilities to CISA.
4. MITIGATIONS
Optigo Networks recommends users to upgrade to the following:
- Visual BACnet Capture Tool: Version v3.1.3rc8
- Optigo Visual Networks Capture Tool: Version v3.1.3rc8
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
- Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls and isolating them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.